序号 |
名称型号 |
型号规格 |
技术参数 |
备注 |
1.1.1 |
干式电力变压器
SCB9–□□□/10
额定容量:30~2500KVA |
SCB9-100/10 |
额定容量:100KVA;额定电压:10±2×2.5%/0.4KV;A组:空载0.45+15%负载1.67+15%总损耗2.12+10%;空载电流1.8+30%短路阻抗:4±10%;绕组温:100K;声功率级:65dB |
B组:空载0.41+15%负载1.8+15%总损耗2.11+10%;空载电流1.7+30% |
1.1.2 |
SCB9-315/10 |
额定容量:315KVA;额定电压:10±2×2.5%/0.4KV;空载0.99+15%负载3.67+15%总损耗4.66+10%;空载电流1.2+30%短路阻抗:4±10%;绕组温:100K;声功率级:69dB |
B组:空载0.88+15%负载3.9+15%总损耗4.78+10%;空载电流1.1+30% |
1.1.3 |
SCB9-630/10 |
额定容量:630KVA;额定电压:10±2×2.5%/0.4KV;空载1.51+15%负载6.22+15%总损耗7.73+10%;空载电流1.0+30%短路阻抗:4±10%;绕组温:100K;声功率级:71dB |
B组:空载1.35+15%负载6.78+15%总损耗8.13+10%;空载电流0.9+30% |
1.1.4 |
SCB9-800/10 |
额定容量:800KVA;额定电压:10±2×2.5%/0.4KV;空载1.71+15%负载7.36+15%总损耗9.07+10%;空载电流1.0+30%短路阻抗:6±10%;绕组温:100K;声功率级:72dB |
B组:空载1.54+15%负载7.8+15%总损耗9.34+10%;空载电流0.9+30% |
1.1.5 |
SCB9-1000/10 |
额定容量:1000KVA;额定电压:10±2×2.5%/0.4KV;空载1.99+15%负载8.61+15%总损耗10.6+10%;空载电流1.0+30%短路阻抗:6±10%;绕组温:100K;声功率级:72dB |
B组:空载1.75+15%负载9.25+15%总损耗11+10%;空载电流0.9+30% |
1.1.6 |
SCB9-1250/10 |
额定容量:1250KVA;额定电压:10±2×2.5%/0.4KV;空载2.35+15%负载10.26+15%总损耗12.61+10%;空载电流1.0+30%短路阻抗:6±10%;绕组温:100K;声功率级:74dB |
B组:空载2.03+15%负载11+15%总损耗13.03+10%;空载电流0.9+30% |
1.1.7 |
SCB9-1600/10 |
额定容量:1600KVA;额定电压:10±2×2.5%/0.4KV;空载2.76+15%负载12.4+15%总损耗15.16+10%;空载电流1.0+30%短路阻抗:6±10%;绕组温:100K;声功率级:75dB |
B组:空载2.7+15%负载13.5+15%总损耗16.2+10%;空载电流0.9+30% |
1.1.8 |
SCB9-2000/10 |
额定容量:2000KVA;额定电压:10±2×2.5%/0.4KV;空载3.4+15%负载15.3+15%总损耗18.7+10%;空载电流0.8+30%短路阻抗:6±10%;绕组温:100K;声功率级:77dB |
B组:空载3.0+15%负载16.2+15%总损耗19.2+10%;空载电流0.7+30% |
1.1.9 |
SCB9-2500/10 |
额定容量:2500KVA;额定电压:10±2×2.5%/0.4KV;空载4.0+15%负载18,18+15%总损耗22.18+10%;空载电流0.8+30%短路阻抗:6±10%;绕组温:100K;声功率级:78dB |
B组:空载3.5+15%负载19.5+15%总损耗23+10%;空载电流0.7+30% |